Selection tables 500 V AC
4.6 Motor starter protector + contactor assembly for star-delta start + 3RB22 / 23 / 3 solid-state overload relay,
or 3UF7
Configuring SIRIUS Innovations
68 Configuration Manual, 04/2010, A8E56203880102-02
Standard
three-phase
motor
4-pole at
400 V AC
1)
Contactors
2)
Stan-
dard
output
P
Motor
current
I
Motor starter
protector
Line contactor +
delta contactor
Star contactor
Overload relay
(solid-state) or
current measuring
module
3)
Setting
range
Overload
release
Overload
relay
kW A Order No. Order No. Order No.
Size
Order No. A
Type of coordination 2 with 3RB22, 3RB23 or 3UF7
5,5 9,2 3RV2311-1JC10 3RT2017-1AP01 3RT2017-1AP01 S00/S00/S00 3UF7101-1AA00-0/
3RB2906-2DG1
2,4 ... 25
7,5 12,4 3RV2311-1KC10 3RT2018-1AP01 3RT2017-1AP01 S00/S00/S00 3UF7101-1AA00-0/
3RB2906-2DG1
2,4 ... 25
7,5 12,4 3RV2311-1KC10 3RT2024-1AP00 3RT2024-1AP00 S00/S0/S0 3UF7101-1AA00-0/
3RB2906-2DG1
2,4 ... 25
11 17,6 3RV2321-4BC10 3RT2026-1AP00 3RT2026-1AP00 S0/S0/S0 3UF7101-1AA00-0/
3RB2906-2DG1
2,4 ... 25
11 17,6 3RV2321-4CC10 3RT2026-1AP00 3RT2026-1AP00 S0/S0/S0 3UF7101-1AA00-0/
3RB2906-2DG1
2,4 ... 25
15 23 3RV2321-4DC10 3RT2027-1AP00 3RT2027-1AP00 S0/S0/S0 3UF7101-1AA00-0/
3RB2906-2DG1
2,4 ... 25
18,5 28 3RV2321-4NC10 3RT2027-1AP00 3RT2027-1AP00 S0/S0/S0 3UF7102-1AA00-0/
3RB2906-2JG1
10 ... 100
Type of coordination 2 with 3RB3
5,5 9,2 3RV2311-1JC10 3RT2026-1AP00 3RT2026-1AP00 S00/S0/S0 3RB3026-1SB0 3,0 ... 12
7,5 12,4 3RV2311-1KC10 3RT2026-1AP00 3RT2026-1AP00 S00/S0/S0 3RB3026-1SB0 3,0 ... 12
11 17,6 3RV2321-4BC10 3RT2027-1AP00 3RT2027-1AP00 S0/S0/S0 3RB3026-1QB0 6,0 ... 25
11 17,6 3RV2321-4CC10 3RT2027-1AP00 3RT2027-1AP00 S0/S0/S0 3RB3026-1QB0 6,0 ... 25
15 23 3RV2321-4DC10 3RT2027-1AP00 3RT2027-1AP00 S0/S0/S0 3RB3026-1QB0 6,0 ... 25
18,5 28 3RV2321-4NC10 3RT2027-1AP00 3RT2027-1AP00 S0/S0/S0 3RB3026-1VB0 10 ... 40
18,5 28 3RV2321-4EC10 3RT2027-1AP00 3RT2027-1AP00 S0/S0/S0 3RB3026-1VB0 10 ... 40
Order numbers for basic versions with screw terminals and spring-loaded terminals also possible.
1)
Guide value for 4-pole standard motors at 500 V AC, 50 Hz. Selection depends on the concrete startup and rated data
of the protected motor.
2)
Rated control supply voltage 230 V AC, 50 Hz, other control voltages possible.
3)
The necessary current measuring modules are specified. The corresponding basic unit 3RB22 / 3RB23 or 3UF7 is
additionally required.