SITOP modular 1ph/2ph
Operating Instructions, 06.2014, C98130-A7548-A1-3-7629
37
Note
Technical data is applicable for a rated input
voltage of 230 VAC, rated load and +25° C
ambient temperature (if nothing else is specified).
6EP1334-3BA10
(24 V/10 A)
6EP1336-3BA00
(24 V/20 A)
6EP1337-3BA00
(24 V/40 A)
Rated voltage value
120...230 / 230...500 V 120...230 / 230...500 V 120/230 V 120/230 V
Voltage range
• Remark
85...264 / 176...550 V
Setting via selector
switch on the device;
starting from Ue >
90/180 V
Derating for -25 to
0 °C:
Starting with max.
85...264 / 176...550 V
Setting via selector
switch on the device;
starting from Ue >
90/180 V
Derating for -25 to
0 °C:
Starting with max.
85...132 / 176...264 V
on the device;
start-up as of Ue >
93/183 V
85...132 / 176...264 V
on the device;
start-up as of Ue >
95/190 V
Power failure buffering
25 ms 25 ms 20 ms 20 ms
Power-failure buffering For Ue = 120/230 V,
typ. 150 ms for Ue =
For Ue = 120/230 V,
typ. 150 ms for Ue =
at Ue = 230 V at Ue = 230 V
Input current / at rated
value of input voltage
2.2 A 4.4 A 7.7 A 15 A
Input current / at rated
value of input voltage
1.2 A 2.4 A 3.5 A 8 A
Input current / at rated
value of input voltage
0.61 A 1.1 A - -