EasyManua.ls Logo

Siemens SITOP series - Test Voltage

Siemens SITOP series
70 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Safety, approvals, EMC
7.2 Test voltage
SITOP modular 1ph/2ph
52 Operating Instructions, 06.2014, C98130-A7548-A1-3-7629
7.2
Test voltage
Figure 7-1 Test voltage diagram
Only the manufacturer can perform the type test and production test; users can also perform
the field test.
Preconditions for performing the field test:
Tests (A) & (B)
Connect the input terminals with one another
Connect the output terminals with one another
Test (C)
Connect the output terminals with one another and measure against PE
Table 7- 1 Test voltages for 6EP1333-3BA10 and 6EP1334-3BA10
Test time
Prim ↔ sec (A)
Prim ↔ PE (B)
Sec ↔ PE (C)
Type test
60 s
4200 VDC
2200 VDC
700 VDC
60 s
3000 VAC
1500 VAC
500 VAC
Production test
1 s
4200 VDC
4200 VDC
500 VDC
1 s
3000 VAC
3000 VAC
350 VAC
Field test
1 s
2200 VDC
2200 VDC
500 VDC
1 s
1500 VAC
1500 VAC
350 VAC
Remark:
Tripping current for DC
measurement: 0 mA
Tripping current for AC measurement: <100 mA

Other manuals for Siemens SITOP series

Related product manuals