EasyManua.ls Logo

Siemens SITOP UPS1100 - Page 147

Siemens SITOP UPS1100
232 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Engineering and remote access
3.7 Web server
SITOP UPS1600 / UPS1100
Manual, 04.2017, A5E37775406-8-76
147
PROFINET interface
You have the option of configuring the PROFINET interface regarding the following points:
General I&M (identification & maintenance)
Defining the location ID
Defining the contact
Defining the device name
Defining whether the IP address is dynamically assigned (activate DHCP) or whether it
should be fixed.
Procedure
1. Select the "Hardware configuration" menu.
2. Select submenu "General".
3. Select the "Communication interface" entry.
4. In the editor area, under "Device name" enter the required device name.
5. To dynamically assign the IP address: Activate checkbox "Source IP address via DHCP".

Table of Contents

Other manuals for Siemens SITOP UPS1100

Related product manuals