EasyManua.ls Logo

Siemens SITOP UPS1100 - Hardware Fault

Siemens SITOP UPS1100
232 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Troubleshooting
4.1 Hardware fault
SITOP UPS1600 / UPS1100
186 Manual, 04.2017, A5E37775406-8-76
4.1
Hardware fault
For an internally identified software or hardware fault/error, the following response occurs:
• LED 1 (O.K./BAT.) lights up red
• LED 2/3/4 are dark
• Alarm 13 (Device failure) is sent
• UPS1600 output shuts down
Response from V2.0.4 or V2.1 and higher:
The output is only shut down for a software error (internal software error, software update
not completed, software checksum is incorrect).

Table of Contents

Other manuals for Siemens SITOP UPS1100

Related product manuals