Page #91 background imageLoading...
Page #91 background image
Engineering and remote access
3.5 Cyclic and acyclic data
SITOP UPS1600 / UPS1100
Manual, 04.2017, A5E37775406-8-76
91
Slot
Subslot
Data
Description
Data size
Battery change
recommended
Battery replacement recommend-
ed: Battery capacity is insufficient
to achieve the specified buffer
time:
0: no
255: yes
Unsigned8
Not used
-
Unsigned8
Battery charge level Battery charge level in %:
0-100: 0-100%
255: unknown battery
Unsigned8
Battery connection
maintenance
from V2.1
Connection to the battery inter-
rupted: Check the connection and
fuse:
0: no maintenance required
255: maintenance required
Unsigned8
3.5.2
Reading and writing data sets
An overview of all data sets, which are communicated between the SITOP UPS1600 and the
PROFINET IO-Controller is provided in the following table. Here, a distinction is made
between the following data sets:
Reading data sets:
Data which is sent from the SITOP UPS1600 to the
PROFINET IO-Controller .
Writing data sets:
Data which is sent from the PROFINET IO-Controller to the
SITOP UPS1600.
Index
Slot
Subslot
Data set
Type
Description
Data size
0x0001 0 1 Buffering parameters Reading /
writing
Buffer parameters.
14 bytes
0x0002 0 1 Battery parameters Reading /
writing
Parameters of the connected battery
modules
5 bytes
0x0003 0 1 Charging parameters Reading /
writing
Charge parameters of the connected
battery modules
4 bytes
0x0004 0 1 Reset parameters Reading /
writing
Reset parameters. 1 byte
0x0005 0 1 Battery information
parameters
Reading
Information about the connected battery
modules SITOP UPS1100. This infor-
mation is available via the link "Energy
Storage".
1024 bytes
0x0006 0 1 Device information
Parameters
Reading Information about the
SITOP UPS1600.
148 bytes
0x0007 0 1 Hardware settings
parameters
Reading Hardware settings of the
SITOP UPS1600 (settings that were
made at the front of the device).
8 bytes

Table of Contents

Other manuals for Siemens SITOP UPS1100

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SITOP UPS1100 and is the answer not in the manual?

Siemens SITOP UPS1100 Specifications

General IconGeneral
BrandSiemens
ModelSITOP UPS1100
CategoryPower Supply
LanguageEnglish

Related product manuals