Engineering and remote access
3.7 Web server
SITOP UPS1600 / UPS1100
154 Manual, 04.2017, A5E37775406-8-76
Basic device configuration
"Buffering" parameters
Parameter
Value range
Initial value
Connection threshold
21 - 25 V
22.5 V
Buffer time
1 - 32767 s
600 s
Maximum buffer time
1)
Yes / No
No
Additional buffer time after PC shutdown.
3)
1 - 300 s
60 s
Expected buffer current
1)
0 - 40 A
0 A
Reset time:
5 s
Enable reset after buffering
Yes / No
No
1)
Parameter only available from SW version V2.0 and higher
2)
Parameter only available from SW version V2.1 and higher
3)
Valid from V2.0.4 or V2.1