Description, device design, dimension drawing
2.6 Electronic overload shutdown and reset
Selectivity modules
24 Manual, 01.2017, C98130-A7579-A1-2-7629
In the range > 150 % of the selected current response threshold, the current is limited to
150 %, typically after 100 ms, the output is electronically shut down (LED of the output is
lit red).
When the output current exceeds the selected current response threshold, and if the
supply voltage simultaneously dips below 20 V, then the output is electronically shutdown
(the LED of the output is lit red).
Shutdown characteristic 6EP1961-2BA51, -2BA61:
Figure 2-12 Shutdown characteristic 6EP1961-2BA51, -2BA61
An output current is continuously permissible up to the selected current response
threshold (LED of the output is lit green).
In the range 101 - 109 % of the selected current response threshold, an overload current
is permissible for 5 seconds (LED of the output flashes green), then the output is
electronically shut down (LED of the output is lit red).
In the range > 110 % of the selected current response threshold, the current is limited to
110 %, typically after 100 ms, the output is electronically shut down (LED of the output is
lit red).
When the output current exceeds the selected current response threshold, and if the
supply voltage simultaneously dips below 20 V, then the output is electronically shutdown
(the LED of the output is lit red).
Reset of an electronic overload shutdown using the reset button and remote reset
Figure 2-13 SITOP PSE200U button