SITRANS P, DS III series (7MF4.33.. 7MF4.34.. 7MF4.35..)
A5E03434656-02, 12/2012
31
9. Close the vent valve on the negative side ①.
10. Open the differential pressure valve
③ by rotating it in half a turn.
11. Check and if required correct the zero point in case of start of scale value 0 bar (4 mA).
12. Close the stabilizing valve
②.
13. Fully open the differential pressure valves
③ and ④.
14. You can briefly open the drain valves
⑦ to clean the line. Close before steam starts to leak.