Commissioning
6.5 Local commissioning
SITRANS LT500 with ultrasonic transducer inputs
Compact Operating Instructions, 02/2024, A5E52021877-AA
83
Step: Select measurement point
Select measurement point
Sets the measurement point to be configured for pump control function.
This step will not appear on a single-point device.
Setting
Measurement point 1
Measurement point 2
Exit
Default
Measurement point 1
Step: Relays currently assigned
Relays currently assigned
Displays any relays that are currently configured for other applications, as a reference of relay
availability for the pump control function.
This step does not appear if no relays are configured for other applications.
Step: Number of pumps
Number of pumps
Sets the number of pumps to configure.
Setting
1
2
3
4
5
6
Default
2