Commissioning
6.5 Local commissioning
SITRANS LT500 with ultrasonic transducer inputs
Compact Operating Instructions, 02/2024, A5E52021877-AA
97
Step: Relays currently assigned
Relays currently assigned
Displays any relays that are currently configured for other applications, as a reference of relay
availability for the alarms.
This step does not appear if no relays are configured for other applications.
CAUTION
Relay conflicts
Notification of relays assigned to other applications is given here, but assigned relays
remain available for alarms. If one of these relays is assigned in the next step, the
assignment from this wizard is used.
When wizard settings are applied in the final step, any relays configured by the alarms
wizard are assigned as needed, including disabling another application if there is a relay
conflict.
If an assignment is made in error, continue to the end of the wizard and select "No" in
the final step ("Apply?"). Then re-run the wizard. (Selecting "Yes" to apply the wizard
settings in this scenario, means the application will be incorrect and relays may be
configured incorrectly.)
Step: Alarm relays
Alarm relays
Enables selected relays for alarms.
Setting
[ ] Relay output 1
[ ] Relay output 2
[ ] Relay output 3
[ ] Relay output 4
[ ] Relay output 5
[ ] Relay output 6
Default [X] indicates enabled by default *
[ ] indicates disabled by default
* Upon entering this step, relays will appear as enabled if they are currently assigned to any
alarm or diagnostic on the current measurement point. Deselecting an already programmed
relay will disable it.