SITRANS P, DS III series (7MF4.33.. 7MF4.34.. 7MF4.35..)
10 A5E03434631-02, 12/2012
WARNING
Open cable inlet or incorrect cable gland
Danger of explosion in hazardous areas.
Close the cable inlets for the electrical connections. Only use cable glands or plugs which are approved for the relevant
type of protection.
WARNING
Incorrect conduit system
Danger of explosion in hazardous areas as result of open cable inlet or incorrect conduit system.
In the case of a conduit system, mount a spark barrier at a defined distance from the device input. Observe national
regulations and the requirements stated in the relevant approvals.
See also
Technical specifications (Page 36)
WARNING
Incorrect mounting at Zone 0
Danger of explosion in hazardous areas.
Ensure sufficient tightness at the process connection.
Observe the standard IEC/EN 60079-14.
WARNING
Danger with "flameproof enclosure" protection
Danger of explosion in hazardous areas. An explosion may be caused by hot gas escaping from the flameproof enclosure
if there is too little space between it and the fixed parts.
Ensure that there is a space of at least 40 mm between the flameproof joint and the fixed parts.
Flameproof joint
WARNING
Loss of explosion protection
Danger of explosion in hazardous areas if the device is open or not properly closed.
Close the device as described in Chapter "Connecting the device (Page 21)".

Table of Contents

Other manuals for Siemens SITRANS P series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SITRANS P series and is the answer not in the manual?

Siemens SITRANS P series Specifications

General IconGeneral
CommunicationHART, PROFIBUS PA, FOUNDATION Fieldbus
Housing MaterialStainless steel, aluminum
Measurement RangeVaries by model (e.g., 0-10 bar, 0-100 bar, etc.)
Output4-20 mA, HART, PROFIBUS PA, Foundation Fieldbus
Operating Temperature-40°C to +85°C (-40°F to +185°F)
Ingress ProtectionIP66, IP67
Measured MediumLiquids, gases
Process Temperature-40°C to +125°C (-40°F to +257°F)
Ambient Temperature-40°C to +85°C (-40°F to +185°F)
ApprovalsATEX, IECEx, CSA
Process Connection1/2" NPT

Related product manuals