Transmitter above the differential pressure
transducer
Transmitter below the
differential pressure transducer
Condition
All shut-off valves are closed.
Procedure
To commission the transmitter for gases, proceed as follows:
1. Open both the shut-off valves
⑥ at the pressure tapping point.
2. Open the stabilizing valve
②.
3. Open the differential pressure valve (
③ or ④).
4. Check and if required correct the zero point when the start of scale value is 0 mbar (4 mA).
5. Close the stabilizing valve
②.
6. Open the other differential pressure valve (
③ or ④).