EasyManua.ls Logo

Siemens SITRANS SL - Safety Characteristics

Siemens SITRANS SL
28 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Device-specific Safety Instructions
Safety Manual
20 Operating Instructions, 06/2012, A5E03433511-05
3.7 Safety characteristics
The safety characteristics necessary for use of the system are listed in the SIL declaration of
conformity. These values apply under the following conditions:
The SITRANS SL is only used in safety-related systems with a low demand mode for the
safety function
When external sensors for process temperature and process pressure are used they
have to be considered as part of the Safety related system.
Purging of sensors must be considered as part of the Safety related system.
The safety-related parameters/settings (see chapter Settings (Page 16)) have been
entered
by local operation and checked before starting safety-instrumented operation.
The SITRANS SL is blocked against unintentional and unauthorized changes/operation.
All used materials are compatible with process conditions.
The MTTR after a device fault is 72 hours.
The logic solver (PLC) has to be configured to detect low range (<3.6 mA) failure of the
SITRANS SL (fail low) and will recognize these as internal failure of the devices and not
cause a spurious trip.
See also
Certificate of Conformity SITRANS SL Functional Safety
(http://support.automation.siemens.com
/WW/view/en/10806991/134200)