PRE-INSTALLATION The following components must be set prior to installing the SSD-C housing enclo-
sure to the SSD-C mounting plate. Refer to Figure 4.
S1 Option Select DIP Switch:
S1-SW1: Set to ON if the SSD-C is the end of the PAIR A wiring (Style 4 only)
S1-SW2: Set to OFF: Not Used
S1-SW3: Set to OFF: Not Used
S1-SW4: Set to OFF: Not Used
S2
S3
S4
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
S11
P1
R70
S1
1
32
ON
4
P2
P3
Figure 4
SSD-C Switch Location
If the SSD-C is located at the end of the wire (Style 4 only), add the terminating
resistance to the communication wire by setting SW1 to the ON position.
S2, S3, S4 Network Address Switches: Set the three-digit HNET network address
for the SSD-C using the three ten-position rotary switches located on the board. (See
Figure 4.) Each of these addresses must be the same as the addresses assigned in
the Zeus Programming Tool. The range of allowable addresses is from 001 to 251
(leading zeros must be used).
S11, Reset Switch: Momentarily Closed switch that when pressed will re-initialize
the SSD-C operation.
R70 LCD Trimmer Adjustment (factory set): Turn to adjust the LCD contrast
asrequired.
If the SSD-C fails, the TROUBLE LED will flash at a fast rate, the sounder will pulse
and no push buttons will respond. The PMI/PMI-2/PMI-3 (XLS), FCM2041-U2 (Desigo
Fire Safety Modular), FCM2041-U3 (Cerberus PRO Modular) detects this failure as a
non-responding module trouble condition.