Building Technologies Boiler sequence controller RMK770 CE1P3132en
HVAC Products 6 Boiler sequence management 23.04.2009
Main menu > Commissioning > Settings > … or
Main menu > Settings > Boiler sequence manager > Control parameters
Operating line Range Factory setting
Downward sequence integral 0…500 K×min 50 K×min
The switching off of a boiler can be impacted by the switch-off integral.
A small switch-off integral means that removal of a boiler from the boiler sequence is
fast.
b
50
47
53
°C
41
44
t
t
swiwtch off
TempMnFlow
TempFlowWDem
TempSeqSwitchDiff
3132D06
TempFlowWDem Flow temperature setpoint for performing the integral
TempSeqSwitchDiff Neutral zone (3 K)
TempMnFlow Main flow temperature
t Time
t switch off Time to elapse for boiler to be switched on
Switching off via the output balance prevents a large number of boilers from operating
at low output although heat demand could be covered by a smaller number of boilers.
Main menu > Commissioning > Settings > … or
Main menu > Settings > Boiler sequence manager > Control parameters
Operating line Range Factory setting
Downward sequence output limit
0…100% --- %
If several boilers maintain simultaneously the same setpoint – e.g. in the case of modu-
lating or 2-stage burners where the individual setpoint boost is set to 0 K or to a very
small value – the output balance is added as a second switch-off criterion.
For 20 minutes, the average boiler output of the boilers in operation must be smaller
than the downward sequence output limit. Also, to ensure that sufficient amounts of
heat can be delivered after boilers have been switched off, it is checked whether the
calculated required output of the boilers remaining in operation would amount to a
maximum of 95%.
Switch-off command via
output balance