A5E32243983 The Probe – INSTRUCTION MANUAL Page 9
mmmmm
English
4 mA calibration
20 mA calibration
Blanking
To change the stored blanking value, obtain the `bL' display.
Press the "20" key to increase or the "4" key to decrease the blanking value.
When the display has scrolled to the desired value, stop pressing the key. The display
automatically returns to the Run mode (6 sec).
4 mA calibration initiated
view stored 4 mA calibration value i.e. 4.50 m
press”20” to increase to new calibration value i.e. 4.60 m
new calibration value
20 mA calibration initiated
view stored 20 mA calibration value i.e. 0.50
m
Note: For faster scrolling, hold the
key depressed during the
calibration adjustment and release
when desired value is obtained.
press “4” to decrease to new calibration
value i.e. 0.45 m
new calibration value
3 sec
blanking
stored blanking value i.e. 0.25 m
press “20” to increase blanking i.e. 0.36 m
Note: For faster scrolling, hold
the key depressed during the
blanking adjustment and release
when desired value is obtained.
press “4 to decrease to desired blanking
value i.e. 0.35 m
6 sec
new blanking value
The Probe
blanking
Blanking is used to ignore the zone in front of the
transducer where false echoes are at a level that
interfere with the processing of the true echo. It is
measured outward from the sensor face. The minimum
recommended blanking value is 0.25 m (0.82 ft) but can
be increased in order to extend the blanking.