A5E32243983 The Probe – INSTRUCTION MANUAL Page 11
mmmmm
English
When the desired option is displayed, stop pressing the key. The display will automatically return
to the Run mode (6 sec).
Fail-Safe Timer
The fail-safe timer allows the user to vary the ‘waiting’ period from the time a loss of echo or
operating fault condition begins, until the fail-safe default is effected. The ‘waiting’ period is
adjustable from 1 to 15 minutes, in 1 minute increments.
The fail-safe timer value will default to settings determined by the speed of response (see page 10).
If a different value is desired, the fail-safe timer should be adjusted
after
the speed of response is
set.
To change the fail-safe timer, obtain the ‘FSt’ display.
Increase the ‘waiting’ period by pressing the “20” key, and decrease it by pressing the “4” key,
stopping when the desired value is displayed.
The display automatically reverts to the Run mode (6 sec).
Units
The units of the measurement reading can be selected as follows:
1 = metres, m (factory setting)
2 = feet, ft
The selected units are also applicable to the `Blanking' adjustment.
To change the units obtain the `Un' display.
Scroll forward through the options ( 1 - 2 ) by pressing the "20" key. Scroll backward through the
options ( 2 - 1 ) by pressing the "4" key.
When the desired option is displayed, stop pressing the key. The display will automatically return
to the Run mode (6 sec).
3 sec
fail-safe
current option i.e. full
Press “20” for option 2 i.e. empty
6 sec
option 2 selected
3 sec
units
current option i.e. m
Press “20” for option 2 i.e. ft
6 sec
option 2 selected