TPS- Installation Instructions for:
Lighting Panelboards Revise P (RP)
If model number includes W option suffix, additional
instructions follow:
The following instructions are for the installation of the
Siemens TPS and L SPD modules in Siemens Revised P
(RP) lighting panelboards.
Be aware of differences between the Revised P
and Original P panelboards. SPDs for Original P
and Revised P are not interchangeable. Original
P panelboards use TPS or L SPDs, whereas
Revised P panelboards use TPS or L SPDs or
the new TPS or L SPDs..
To determine if a customer has a Revised P panel
– look at the part number of the interior. If the
part number ends with “N” or “T” then it is a
Revised P. If it does not end in either “N” or
“T” then it is an Original P panel. For example:
PEMCA is an Original P panel and
PEMCAT is a Revised P panel. If it is a
Revised P panel ending in “N” – then there is
no Subfeed space and no place for an SPD to be
installed internally. A different SPD like the new
Bolthshield BSPD product line can be an option
for the Revised P panel ending in “N” because
it mounts in a unit space.
Item Description Qty. Torque
TPS
TPS Mounting Plate
#- Hex Screw w/captive washer in-lb
#- Hex Thread Rolling Screw in-lb
TPS Phase Tabs (part of TPS unit) * or
#/- Hex Screw w/captive washer * or in-lb
Neutral Lug Wire Connection N/A in-lb
” # AWG White Neutral Conductor
*only 2 tabs for single phase modules
Figure : Revised P Panel
1
2
3
4
5
6
7
8
Figure : Revised P Panel Phase Tab Detail
Step ) Lock off all power supplying this equipment before
working on it.
Step ) Attach TPS Mounting Plates (Item , Places) to
TPS using - SEM screws with captive lock washers
(Item ). The mounting plates should be attached to the
TPS with the offset oriented towards the top of the unit.
Torque Screws to values listed.
Step ) Position the TPS unit (item ) on the panel base rail
so that the TPS Phase tabs (Item ) extend beneath the Bus
Tabs on RP Panel. Attached TPS Phase Tabs to Panel Bus
using #/- Hex SEM Screws (Item ). Do not Torque at
this time.
Step ) Connect the TPS unit to the base rail using four ()
of the #- Hex Thread Rolling screws (item ).
Step ) If present, connect TPS Neutral Connection Lug
(Item ) to Panel Neutral using AWG minimum wire.
For best SPD performance, trim wire as required to provide
shortest possible route between TPS Neutral connection
and Panel Neutral Connection. Route wire as straight as
possible and use gentle radius on any bends. Do not kink
wire. Prevent wire from encroaching breaker locations.
Neutral Connection is not applicable on Delta systems.
Step ) Torque all connections to the values as specified on
the installation.
Table : Content for Installation in Lighting Panelboards
Revised P
TPS- Surge Protection Device | Installation Guide / User Manual