6 - USE
Low limit Indication of an error when it drops below a certain value
Installer Value Value
Sensor calibration Positive or negative offset for calibrating a sensor
Installer -150...150 0 K
HW lter PT1 N/A
Installer 0...28800 0 s
High limit High error threshold
Installer -50...150 150 °C
Low limit Low error threshold
Installer -50...150 -50 °C
Alarm cong N/A
Factory 0x01FF
Outputs
Installer
Alarm delay Delay in signalling a sensor alarm
Installer 0...3600 0 s
Outdoor sensor Same menu as for “Water heater sensor”
Installer
Zone1 sensor Same menu as for “Water heater sensor”. Visible only if Conguration>Zones>3 way valve> Type of Zone=Mix.
Installer
Zone2 sensor Same menu as for “Water heater sensor”. Visible only if Conguration>Zones>3 way valve> Type of Zone=Mix.
Installer
Zone3 sensor Same menu as for “Water heater sensor”. Visible only if Conguration>Zones>3 way valve> Type of Zone=Mix.
Installer
Zone4 sensor Same menu as for “Water heater sensor”. Visible only if Conguration>Zones>3 way valve> Type of Zone=Mix.
Installer
Zone5 sensor Same menu as for “Water heater sensor”. Visible only if Conguration>Zones>3 way valve> Type of Zone=Mix.
Installer
Zone6 sensor Same menu as for “Water heater sensor”. Visible only if Conguration>Zones>3 way valve> Type of Zone=Mix.
Installer
DHW tank sens Same menu as for “Water heater sensor”
Installer
Solar panel sensor Same menu as for “Water heater sensor”
Installer
DHW return sensor Same menu as for “Water heater sensor”
Installer
Solar tank sens Same menu as for “Water heater sensor”
Installer
0-10V Module1 0-10V output setting for heat generator 1
Installer
Manual control Automatic or manual control of the output
Installer Auto; 0...100 % Auto
Actual value Output value percentage of the 0-10V signal
Installer Value Value
Error Possible output error
Installer Value Value
0-10V Module2 Same menu as for “0-10V Module1”
Installer
0-10V Module3 Same menu as for “0-10V Module1”
Installer
0-10V Module4 Same menu as for “0-10V Module1”
Installer
Tank pump Domestic hot water tank pump control relay
Installer
Manual control Manual or automatic control of the relay
Installer Off; On; Auto; Auto
Actual value
Installer Value Value
Error Possible output error
Installer Value Value
_+operating hours
Installer 1 h 1 h
Operation (Reset) N/A
Installer Execute Execute
Last heat.sys.hour N/A
Installer Value Value
> Value Date N/A
Installer
Contact function Normally closed or open function of the contact
Installer NO...NC NO
DHW return pump Same menu as for “Tank pump”
Installer
Zone1 pump Same menu as for “Tank pump”
Installer
Zone2 pump Same menu as for “Tank pump”
Installer
Continued on the next page