4 Analog input functions
4.1 Measurement
The following analog variables can be processed:
– Temperature, via resistance sensors
– Resistance
– Voltage
– Current
Configurable signal types
over range
6)
LED
4)
AI Pt1000 P1K
1)
AI PT1K375
Pt1K 375 -50...150
1) 7)
-52.5 ...185 °C
10 mK OFF Sensor type
x x x x
AI PT1K385
Pt1K 385 -50...400
1)
-52.5...610°C 20 mK OFF Sensor type
2), 8)
(600) °C
1)
AI NTC10K NTC10K -50...130
1)
-52.5...155 °C 10 mK OFF Sensor type
µ
µ
1) (180) (600) (150) and NTC only with reduced hum injection, see [6]
2) The signal types AI Pt100, AI Pt100 4 wire and AI 250 Ohm run on the TXM1.8P module only, which has no LCD
display.
In the case of direct island bus integration, AI Pt100 4 wire and AI Pt100 are connected with 4 wires, AI 250 Ohm
with 2 wires.
In the case of P-bus BIM integration (V4), AI Pt100 (P100) is connected with 4 wires, AI 250 Ohm (R250) with 2 wires
and jumpers to 4 terminals (as PTM-I/O); connection diagram see data sheet N8176.
The resolution with island bus is significantly better than with P-bus BIM.
4) The "unreliable (general)“ error message is displayed:
– when AC 24 V (terminal V
) for field supply is not available or low (AI 0-10V)
– when DC 24 V (terminal V
, CS) for field supply is not available or low (AI 4-20mA, AI 0-20mA)
5) For 25 mA use signal type AI 0-10V and install a shunt of 400 Ohms (1 W, 0.1 %). Details: [7].
6) When the process value is out of range, an error message will be sent.
7) AI PT1K375: No restriction concerning hum injection for TXM1.8U und TXM1.8X.
8) An open circuit of a single conductor cannot be detected for these signal types.