26/54
Siemens TX-I/O™ Module system – Functions and operation CM110561en_08
Building Technologies Digital output functions 2018-10-25
5 Digital output functions
5.1 General information on the digital outputs
The following functions for digital outputs are available in the TX-IO™ range:
BO Relay NO 250V
BO Relay NC 250V
(Section 5.2)
Q250
Maintained contact, relay, changeover
(also control of Step switches, pulse switches, bistable relays)
BO Triac NO
BO Triac NC
(Section5.3)
-- Maintained contact, triac
Control of AC 24 V devices, especially thermic and motoric actuators
Admissible load per I/O point: see data sheet N8179.
BO Bistable NO / NC
(Section 5.4)
-- Maintained contact, bistable (for lighting applications,
behavior in case of power fail and bus fail can be parameterized)
BO Pulse On-Off
(Section 5.5)
Q250-P /
Q250A-P
On/off pulse, N/O and N/C contact
BO Pulse
(Section 5.6)
-- Pulse
MO Steps
(Section 5.7)
Maintained contact
;
mutually exclusive electronic relay interlock
MO Pulse
(Section 5.8)
Q-M1…M4 Multistate pulse
mutually exclusive electronic relay interlock
BO 3-Pos Relay
BO 3-Pos Triac
(Section 5.9)
Y250T
Pulse, control signal, three-position output, internal stroke algorithm
BO PWM
(Section 5.10)
-- Pulse width modulation, output AC 24 V
BO Blind Relay
(Section)
-- Maintained contact relay, blinds control with 2 / 3 end switches
Admissible load per I/O point: see data sheet N8178.
1)
Feedback must be implemented using separate inputs
All relays in TX-I/O modules are equipped with changeover contacts.
Exceptions:
• TXM1.6RL, see section 5.3)
• TXM1.8RB, see section 5.11)
Local Override
Process
value
Signal Processing
I/O status LED
LO LED
BUS
10561Z207
LED color
Normal
Service
Alarm
Block diagram of function