Building Technologies Default functions, disabling function 2018-10-25
7 Default functions, disabling function
7.1 Default functions
The default functions are downloaded into the modules before they leave the factory.
They permit reduced operation and convenient "functional testing" in the control panel
before the module parameters have been set.
The various modules have the following default functions:
Description see next page
Description see next page
Resistance measuring
TXM1.8P RI Default Description see next page
Relay modules TXM1.6R, TXM1.6R-M,
BO Default BO Relay NO 250V / Q250
4 x MO Steps (2-stage) / Q-M2
The default functions (factory-set I/O module status) have been specially designed for
testing without a bus master. With configured modules, each I/O point would react
differently according to the signal type.
The default functions allow you to test the wiring that is connected to the I/O points, as
soon as the DC 24 V supply is switched on (no connection to a bus master is required).
When the module is powered, the module status LED flashes.
When additionally the address key is swiveled in, the default function is available.
7.2 Null function (Null Function)
The disabling function prevents local override of an I/O point. It should be configured to
decommission any unused I/O points.
There are no variables to set as parameters, and no island bus inputs or outputs.