48/54     
Siemens  TX-I/O™ Module system – Functions and operation  CM110561en_08 
Building Technologies  Digital output functions  2018-10-25 
Static commands 
UP 
UP  The commands can have an 
additional pulse at the end 
DOWN  to middle position (3
rd
 end switch) 
Relative commands 
RUN_UP 
These commands contain one direction only (UP, DOWN) and one 
pulse length. They are used specifically to change the louver angle 
using short pulses in blinds with louvers.  
Relative commands can also be parameterized for long pulses. 
  RUN_DOWN 
Absolute command 
RUN_ABS 
If the blinds drive to a defined position with the help of the calculated 
pulse length on outputs n or n+1 
Position and status for the blinds and the I/O function are returned to the bus master 
Various 
CAL 
Command to drive the blinds once all the way to the top and to the 
bottom to (by measuring motor current) determine the runtime 
RunTimeDownUp (calibration) 
Position query from bus master 
 
 
Normally, preparameterized outputs are used customized to the actuators to be 
operated.  
The following parameters are available for individual parameterization: 
Parameter  Description  Range  (default) 
RunTimeDownUp 
Runtime from Down2 to Up  1...655 s  (180 s) 
RunTimeUpDown 
Runtime from Up to Down2  1...655 s  (180 s) 
RunTimeDown1Down2 
Runtime from Down1 to Down2  1...655 s  (1.5 s) 
BreakTime  Break between opening a relay and closing an other 
relay (change of ditection) 
0.2...25.5 s  (0.5 s) 
EndPosDetection  Detection of the end positions by measuring the motor 
current on the relay outputs 
Inactive, Active, Once  
MotorDelay  Delay between pulse start and motor action. Some 
motors take a certain time before they consume current. 
This parameter prevents the current detection from 
assuming that the motor is in end position or that there 
0.01...2.55 s  (0.1 s) 
Delay between pulse end and blinds stop (UP) 
Delay between pulse end and blinds stop (DOWN) 
BackupMode  Backup status in case of master down  
Keep  =  Last 
command 
No      = Relay inactive 
Value =  AOBBackup 
Value