Whichever first switches from “Unit Off” to “Power saver off” or “Power saver on”, it will power the
inverter on.
If the commands from the two panels conflict, the inverter will accept command according to the following
priority:
Power saver on> Power saver off> Power off
Only when both panels are turned to “Unit Off” position, will the inverter be powered off.
The suggested length between the switch panel and inverter is 10 meters.
Never cut the remote cable when the cable is attached to inverter and battery is connected to the inverter.
Even the inverter is turned off, this will damage the remote PCB inside if the cable is short circuited during
cutting.
LCD remote control panel(optional).
Note:
When the inverter is in Battery Priority mode, “AC: abnormal” will also be displayed when the inverter
finishes a complete charging circle and switches to inverter mode.
“AC: abnormal” only means the inverter doesn’t accept AC input or there is no AC input, it doesn’t mean
the inverter is abnormal.
In AC mode, the LCD will not display the status of AC load.
2.5.8 Audible Alarm
The inverter also gives audible alarms when the following situations occur.
(1)110%<load<125%(±10%), No audible alarm in 14 minutes,
Beeps 0.5s every 1s in 15
th
minute and Fault after 15 minutes;
(2)125% <load<150%(±10%), Beeps 0.5s every 1s and Fault after 60s;
(3)Load>150%(±10%), Beeps 0.5s every 1s and Fault after 20s;