4.4 Trouble operation
When the trouble condition occurs, the control unit's operator interface shows the following:
The yellow SYSTEM TROUBLE LED starts flashing.
You can see the different LEDs to see specific troubles:
- If there are troubles on the IDC zone, the respective zone’s yellow TROUBLE LED starts flashing.
- If there is AC loss, the green AC POWER LED turns off.
- If there are battery faults, the yellow BATTERY TROUBLE LED starts flashing.
- If there are ground faults, the yellow GROUND FAULT LED starts flashing.
- If the system is disabled, the respective yellow DISABLED LED starts flashing.
The local piezo produces a steady tone.
The system activates the general trouble relay.
Communicate the trouble condition to the central station, and the remote station if programmed.
The system stores a trouble event in the history file.
When you press the ACK key, the following actions occur:
The SYSTEM TROUBLE LED and all other specific trouble indicators illuminates steady.
The local piezo turns off.
The system stores an acknowledged event in the history file.
The following are latch-able trouble:
NAC over current Trouble: NAC short during alarm condition
Recovery steps:
Clear the alarm condition and reset the panel.
Reset the panel again to clear the trouble.
page 9 579-1403 Rev A
2004 Foundation Series Fire Alarm Control Unit Operation Guide

Other manuals for Simplex 2004 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simplex 2004 Series and is the answer not in the manual?

Simplex 2004 Series Specifications

General IconGeneral
BrandSimplex
Model2004 Series
CategoryControl Unit
LanguageEnglish

Related product manuals