EasyManua.ls Logo

Simplex 4006-9121 - Alarm Groups

Simplex 4006-9121
78 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 1. Overview
1-6
Alarm Groups
Alarm groups allow you to implement basic selective signal-
ling applications. As you program input (zone of smoke
detectors) and output points (NAC or relay), you are given
the opportunity to associate the point with an alarm group
number. The number can range from 1-100 and each point
can be in up to three alarm groups. When programming is
complete, an initiating device can only trigger the output
devices (relays, NACs) that share its alarm group(s).
Technical Manuals Online! - http://www.tech-man.com

Table of Contents

Related product manuals