Chapter 2. Installation and System Checkout
2-12
City Connect Module Wiring
• City connect module mounts to the main system as 
shown. Refer to City Module Installation Instructions 
for details.
• City module consists of two circuits that are jumper-
configured. Circuits may be configured for reverse-
polarity or local energy operation. See jumper setting 
table for details. Modules must also be added to the sys-
tem configuration. See “System Options” later in this 
manual.
• All wiring to be per NPFP-72, NEC, and local codes. 
Minimum 20 AWG for reverse polarity; minimum 18 
AWG for local energy circuits.
• Conductors must test free of all grounds.
• Wiring is supervised for opens and grounds, but not 
power-limited.
• For specific information about reverse polarity and local 
energy circuits, see Figure 2-13.
• If wiring is routed outside the building, use of a listed 
secondary protector is required. Use Simplex 2081-
9028 or 2081-9044. A protector must be installed at 
each building exit/entrance. Each 2081-9028 adds .2 
ohms wiring resistance. 2081-9044 adds 6 ohms wiring 
resistance. Use of 2081-9044 will greatly reduce wiring 
distance.
• Circuits are shipped with 3.3K, 1/2W resistor installed. 
Remove resistor before wiring circuit. Leave installed 
on unused circuits.
 Figure 2-13    City Connect Module Wiring
EMPLOY A 14.5 OHM TRIP COIL. 
P5
LE
RP
LE
RP
P4
10 9
8 7
6 5
4 3
2 1
P3
LE
RP
LE
RP
P2
10 9
8 7
6 5
4 3
2 1
P6
1
2
3
4