Introduction
4007ES Series Fire Detection and Control Panels
provide extensive installation, operator, and service features
with point and module capacities suitable for a wide range of
system applications. Panels can be configured for stand-alone
or networked fire control operation. The convenient and
intuitive color touchscreen provides easy access for typical
system response actions and for detailed system review or
configuration updates with password control to limit user
access.
Flexible for new and retrofit applications. Standard
conventional IDCs and addressable IDNet+ communications
provide flexibility for both new and retrofit systems. IDC and
NAC end-of-line resistor values are selectable to match a wide
range of existing initiating device circuits and notification
appliance circuits.
Operator Interface
Convenient Status Information. With the locking door
closed, the glass window allows viewing of the display status
LEDs. The user interface is a 4.3” diagonal color touchscreen
LCD with separate status LEDs as shown below.
LED indicators describe the general category of activity being
displayed with the LCD providing more detail. For the
authorized user, unlocking the door provides access to the
control functions and allows further inquiry by scrolling the
display for additional detail.
Operator Interface and Software Features
Convenient and detailed operator information is easily
accessed using a logical, menu-driven touchscreen display
with password access control
Multiple automatic and manual diagnostics for maintenance
reduction
Operator Interface Features (Continued)
Alarm and Trouble History Logs (up to 1000 entries for
each, 2000 total events) are available for viewing from the
display or for printing to a connected printer, or downloaded
to a service computer
Module level ground fault searching assists installation and
service by locating and isolating modules with grounded
wiring
WALKTEST silent or audible system test performs an
automatic self-resetting test cycle and supports up to 8
WALKTEST groups
Install Mode allows grouping of multiple troubles for
uninstalled modules and devices into a single trouble
condition (typical with future phased expansion); with
future equipment and devices grouped into a single trouble,
operators can more clearly identify events from the
commissioned and occupied areas
Mechanical Description
Locking door with acrylic insert
Latching front panel assembly swings forward for
convenient internal access
Smooth box surfaces are provided for locally cutting
conduit entrance holes exactly where required
Modules are power-limited (except as noted, such as
relay modules)
Battery compartment (bottom) accepts two batteries, up
to 18 Ah, to be mounted within the cabinet without
interfering with module space; charger capacity is up to
33 Ah; for batteries greater than 18 Ah, refer to page 6
for external battery cabinet details
Cabinet assembly design has been seismic tested and is
certified to IBC and CBC standards as well as to ASCE 7
categories A through F, requires battery brackets as
detailed on data sheet S2081-0019
2 S4007-0001-10 1/2017
Touchscreen Display with LED Status Indicators (approximately full size)
AlarmIndicator
RedLED
Priority2Indicator
redLED
SupervisoryIndicator
yellowLED
TroubleIndicator
yellowLED
ACPower
green LED
Color
touchscreenLCD
3programmableLEDswithcustomlabel
insert;toptwoselectableas
redoryellow,bottomselectableas
greenoryellow
AlarmSilencedIndicator
YellowLED