Simplex 4007ES - Chapter 2: Installation; Mounting the 4007 ES Panels

Simplex 4007ES
8 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
16" (406 mm)
20-7/8" (530 mm)
20-3/16"
(512 mm)
4-7/16" Deep (112 mm)
Exposed box for semi-flush mounting
1-3/4" (44 mm) minimum
Side View Reference
Finished wall surface (including
semi-flush Trim Kit if used)
A
B
E
F
J K
I
D
H
G
L
C
M
Module Locations:
A. CPU and User Interface assembly.
B. Location for optional 4007-9805 LED Module.
C. Power Supply Assembly.
D. 4007-9806 SDACT location. Note: The SDACT includes a 650-1838 flat mounting bracket (available separately). Some pre-existing
systems with an angled SDACT bracket will need to be replaced with the flat mounting bracket when a Network Interface Card is installed.
E. Location for 4007-9801 Zone/Relay Module, 4007-9812 Dual RS-232 Interface, or (as shown) 4007-9802 25 V Regulator Module
F. Primary location for 4007-9801 Zone/Relay Module, or 4190-6106 TrueInsight Remote Service Gateway.
G. Location for additional 4007-9801 Zone/Relay Module.
H. Identical to Block G above.
I. 4007-9807 or 4007-9808 City Circuit Module, or 4007-9809 Relay Module.
J. 4007-9803 IDNet+ Loop Expansion Modules, maximum of two (two are shown).
K. Identical to block J above.
L. Block L is an additional block that sits on spacers above Block G and H. The 4007-9810 NIC can be mounted in block L with or without
modules mounted below it in blocks G and H. When fiber media cards are used and an SDACT is present, the SDACT requires a 650-
1838 flat mounting bracket (ordered separately).
M. Battery location for up to 18 Ah batteries. Note: No conduit entry or wiring in this area, 14-7/8” (378 mm) wide.
Note: A system ground must be provided for Earth Detection and transient protection devices. This connection shall be made to an
approved, dedicated Earth connection per NFPA 70, Article 250, and NFPA 780.
Custom Background Display Details
Supported file types: JPG, BMP, GIF, and PNG
Recommended image type is JPG, recommended image size is 480 x 240, and
the file size limit is 100 kb
Environmental
Operating Temperature 32° to 120°F (0° to 49° C)
Operating Humidity Up to 93% RH, non-condensing @ 90° F (32° C) maximum
Additional Technical Reference
Description Document Description Document
Installation Manual 579-1102 Single Page Operator Instructions 579-1109
Zone/Relay Module Installation Manual 579-1103 2-Wire Detector Compatibility Chart 579-832
Detailed Operator’s Manual 579-1165
7 S4007-0001-10 1/2017
4007ES Mounting and Module Location Reference