4100-3109 IDNet 2, 4100-3110 IDNet 2+2 and 4100-3111 IDNet Loop card Installation Instructions
Configuring the Point Editing Tab
The next tab is the Point Editing tab. This tab is used to manage and edit the point types that correspond to the devices on the IDNet loop.
Refer to the 579-849 ES Panel Programmer manual for information and instructions on how to proceed.
Figure 12: Point Editing Tab
Configuring the Loop Editing Tab
The Loop Editing tab determines the configuration of the loops.
When the IDNet 2 card is added to the ES Programmer, the programmer automatically reserves four specific addresses for the four potential loops.
Loop 1: Point 251
Loop 2: Point 252
Loop 3: Point 253
Loop 4: Point 254
The device type for both Loop 1 and Loop 2 is set to ISO and cannot be edited.
The device type for Loop 3 and Loop 4 is set to UNUSED by default and must be set to ISO for those loops to be activated.
Once the device type has been determined the following fields may be completed:
Custom Label
Alternate Custom Label
Primary Action Message
Trouble Action Message