page 5 579-1169 Rev E
4100-3109 IDNet 2, 4100-3110 IDNet 2+2 and 4100-3111 IDNet Loop card Installation Instructions
Installation
Mounting
The IDNet 2 card and the IDNet 2+2 card mount onto the Power Distribution Interface (PDI) in an FACP expansion cabinet. The IDNet 2 card can also
be installed in the expansion slot of an ES Power Supply Card (ES-PS) card.
To mount the IDNet 2 and IDNet 2+2 card:
1. Select an empty PDI connector. Insert the washer and the metal standoffs into the corresponding installation holes.
2. Insert the PDI connector on the back of the card into the PDI connector.
3. Use the provided hardware to secure the card.
PDI Connector
(Reverse Side)
#6 Screws
Standoffs
Washers
PDI
Figure 4: Mounting an IDNet 2 or IDNet 2+2 card (IDNet 2 card shown)
To add IDNet Loop cards to an IDNet 2 card:
1. Remove the screws that attach the IDNet 2 card to the panel.
2. Insert the metal standoffs and the plastic standoffs into the corresponding installation holes.
3. Insert the connector on the back of the IDNet Loop card into the connector on the IDNet 2 card and snap it in place with the plastic standoff.
4. Use the provided hardware to secure the card.
Note: When adding IDNet Loop cards to a pre-installed IDNet 2 card, it is important to remember that the properties of the IDNet 2 card must be
updated in the FACP programmer.
IDNet Loop Card
IDNet 2 Card
Plastic Snap-In
Standoff
Metal
#6 Screw
Standoffs
Connector
(Reverse Side)
IDNet Loop Card
IDNet 2 Card
Figure 5: Adding an IDNet Loop Card to an IDNet 2 Card