6-11
Table 6-1. Reports (continued)
Report Description
TrueAlert Status Report
This report can be created after the TrueNAC
Voltage Drop Test (see Chapter 7) is run. It reports
the following information for each Multi Candela
TrueAlert Device.
Point ID
Custom Label
Pass/Fail
Report the following information for each SLC
Nominal Current (A) - The current draw on the
TrueAlert circuit when the test was run.
Worst Case Current (A) - The current draw on the
SLC under worst case operating conditions.
Worst Case voltage Above/Below threshold (V)
TrueAlarm CO Report
This report provides the following information
regarding the CO devices:
Device Number (on the network)
Custom Label (custom description of device)
Current Device Value (PPM)
End-of-Life Date
Device Status (Normal, Trouble)
Install Mode List Report
This report provides the following information
regarding the Install Mode list:
Point ID
Custom Label
Device Status
Alarm Verification Tally
Report
This report provides the following information for each
device supporting alarm verification:
Device Number
Custom Label
Device Type
Point Type
Tally Count
1. Press the MENU key. Use the NEXT and PREVIOUS keys to scroll through the choices
until the “PRINT REPORTS?” choice is displayed.
2. Use the NEXT and PREVIOUS keys to scroll through the categories of report (Alarm
History, Trouble History, etc.).
3. When the category of report you want to print is displayed, press ENTER. The system
prompts you to confirm that you want to generate the report. Press ENTER again.
The report prints on the panel’s report printer.
Printing Reports,
Continued
Overview
100B
Procedure
firealarmresources.com