9-4
1. Press the All Speakers Talk button. The LED associated with this button illuminates, along
with the LEDs for each of the speaker circuits.
2. Key the microphone (depress the talk switch) and wait for the Ready to Talk LED to
illuminate. When this LED is ON, talk into the microphone. The page is routed to all speaker
circuits connected to the system.
1. Key the microphone (depress the talk switch).
2. Wait for the Ready to Talk LED to illuminate. (It will not illuminate until the evacuation
message has finished playing.)
3. Speak into the microphone to page the floors being evacuated.
While an evacuation is in progress, you can page additional floors. To do this, follow these steps.
1. Press the buttons associated with the additional floors prior to keying the microphone. The
LEDs associated with these floors turn ON.
2. Key the microphone and wait for the Ready to Talk LED to illuminate. Once this LED
illuminates, speak into the microphone. The message is played on the additional floors.
1. Press the button labeled “Local Speaker” to hear what is being played at that time. The LED
associated with this button illuminates when the button is pressed to indicate the function is
active.
Note: If the user picks up the local phone or keys the microphone while the local speaker is
active, the speaker shuts off to prevent feedback. Following local phone or microphone use,
the local speaker must be manually turned back on if operation is required.
Press the Alarm Silence button on the front panel to silence the audio system. When you do this,
the speakers remain on, but play nothing.
Press the System Reset button to reset the audio system. When you do this, the following occurs.
All speakers and associated LEDs turn OFF.
The local speaker turns off.
Any paging that is in progress is canceled.
Single Channel Audio Operation,
Continued
130B
Page Entire Building
131B
Page Only Floors
Being Evacuated
132B
Page Additional
Floors
133B
Listen to What is
Being Played Using
the Local Speaker
134B
Silencing the Audio
System
135B
Resetting the Audio
System