$02SAVE Permanently save the settings to flash memory.
*2=SAVE_TO_
FLASH Hawk 3 response.
To verify last setting change:
$02RA1 Read alarm 1 settings.
*2=HI 12.00,SP_
DELAY=H2000ms,
L500ms,RELAY=ND Hawk 3 response: High setpoint at 12.000 with a Hi delayed
esponse of 2.0 seconds, a Lo delay of 0.5 seconds and
a normally de-energized relay.
$02LP3 Set the number linearization points to 3.
*2 Hawk 3 Response
$02L1E040.00D000.00 Linearization point 1 electrical input is 4000
counts, display shows 0.
*2 Hawk 3 response.
$02L2E120.00D050.10 Linearization point 2 electrical input is 12000
counts, display shows 50.10
*2 Hawk 3 response.
$02L3E200.00D100.00 Linearization point 3 electrical input is 20000
counts, display shows 100.00
*2 Hawk 3 response.
$02EXIT Terminate menu settings, save changes and
resume normal operation.
*2=UPDATE_RAM Hawk 3 response.
NOTE: After linearization changes, the Hawk 3 permanently saves the changes
to flash memory.
To verify last setting change:
$02RL
*2=,(1)E= 40.00,(1)D= 0,(2)
E= 120.00,(2)D= 50.10,
(3)E= 200.00,(3)D= 100.00 Hawk 3 response