6
Technical Information
Service Manual
2.2 Capacity V
ariation Ratio According to Temperature
2.3 Cooling and Heating Data Sheet in Rated Frequency
Capacity ratio(%)
Cooling
Cooling
Capacity ratio(%)
Outdoor temp.(°C)
Heating
Capacity ratio(
%)
Outdoor temp.(°C)
Heating
Capacity ratio(
%)
Outdoor temp.(°C)
Heating operation ambient temperature range is -15ºC~24ºC
Outdoor temp.(°C)
Heating operation ambient temperature range is -22ºC~24ºC
0
20
40
60
80
100
120
140
010152025-15-10 -5 5303543
80
100
120
140
0510-15-10 -5 15 20 25 30 35 43
0
80
100
120
140
0 2 7 15 18 21-22 -15 -10 -7 24
Conditions
Indoor:DB20°C
Indoor air flow:Super High
Pipe length:5m
0
20
40
60
80
100
120
140
0 2 7 15 18 -22 -15 -10 -7 21 24
tionsCondi
0°:DB2rIndoo C
gper Hiow:Suair flrIndoo h
5mength:Pipe l
ononditiC
5mngth:pe lePi
DB27°door:In C B19°W C
w:air flodoorIn
ghHi
Instruction:
T1: Inlet and outlet pipe temperature of evaporator
T2: Inlet and outlet pipe temperature of condenser
P: Pressure at the side of big valve
Connection pipe length: 5 m.
Cooling:
Rated cooling
co
ndition(°C) (DB/WB)
Model
Pressure of gas pipe
connecting indoor and
outdoor unit
Inlet and outlet pipe temperature of heat
exchanger
Fan speed of
indoor unit
Fan speed of
outdoor unit
Indoor Outdoor P (MPa) T1 (°C) T2 (°C)
27/19
35/24
SIH+SOH-09BIR2
0.8 to 1.1 12 ~ 15 68 ~ 38
TURBO
High
SIH+SOH-12BIR2
0.9 to 1.1 12 ~ 14 75 ~ 37
Heating:
Rated cooling
co
ndition(°C) (DB/WB)
Model
Pressure of gas pipe
connecting indoor and
outdoor unit
Inlet and outlet pipe temperature of heat
exchanger
Fan speed of
indoor unit
Fan speed of
outdoor unit
Indoor Outdoor P (MPa) T1 (°C) T2 (°C)
20/- 7/6
2.8 to 3.2 63 ~ 35 2 ~ 5
TURBO
High
2.2 to 2.4 70 ~ 35 2 ~ 4
SIH+SOH-09BIR2
SIH+SOH-12BIR2