Operation instructions
SIPOS 5 PROFITRON, HiMod
Page 48 Y070.020/GB
6 Parameters and possible parameter values
6
Parameters and possible parameter values
Parameter
Default value
Explanation
Parameter value Other param.
remote reconnect
non-active
The „remote reconnect“ parameter enables the change-over to a second control mode, to change,
e.g. in case of an error, from analog to binary control. As a prerequisite, „PulsCont BinInp“ must
not be selected for the „remote control“ parameter. The change-over is performed for an active
binary STOP signal.
non-active Change-over to a second control mode is not possible.
The control mode (parameter) selected via the „ remote control“ parameter
is active.
PosCntr CurrInp For an active binary STOP signal the control mode changes from the
parameter value of the „remote control“ parameter to the selected control
mode.
(If the binary STOP signal is not active, the control mode (parameter
value) selected via the „remote control“ parameter is active.
PosCntr bus inp.
tri-threshold
PermCont BinInp
PermCont bus
two-wire-control
non-active
PosCntr CurrInp
DCS-setpt-custom
Linear
Selection is only
displayed if for
remote control (see
above) „PosCntr
CurrInp“ or „PosCntr
bus inp.“ was
selected.
For the default setting
of the setpoint input
„rising/falling“, it is
possible to adapt the
curve and to deviate
from the linearity. The
actual value feedback
is adapted using the
DCS-actvl-custom
parameter.
Fig.: Two basic interpretations of the DCS setpoint: „Slow opening“
and „quick opening“
DCS-setpt-custom
Linear
Identical to default setpoint curve.
LT-Sollw-Anpassg
Equal percentage
The actual position value (of the actuator) slowly follows the setpoint, see
illustration on the left.
DCS-setpt-custom
Quick opening
The actual position value (of the actuator) precedes the setpoint, see
illustration on the right.
DCS-actvl-custom
ActVal= Position
If the setpoint adaptation has been set to slow or quick opening for the „DCS-setpt-custom“
parameter, the actual value can be adapted accordingly.
DCS-actvl-custom
ActVal=Position
The ACTUAL value signaled to the DCS corresponds to the actuator
position.
DCS-actvl-custom
ActVal=acc.setpt
The ACTUAL value signaled to the DCS corresponds to the de ned
setpoint.
proport.run time
autom.determin.
Only for remote control with parameter values „proportion.conv“ or „proportion. bus“.
A prerequisite for proportional operation is that the positioning time (run time), i.e. the time the
actuator requires to cover the whole travel, is known. The time can either be determined by the
actuator itself or measured and de ned by the user.
Proportional operation is supported from rmware version 2.40.
autom.determin. Automatic determination of the run time. The run time will automatically be
determined after any end position adjustment or changes in the rise time.
For this, the actuator has to be operated at least 3 % of the travel.
user-de ned Different run times for OPEN and CLOSE may be de ned.
run time CLOSE Possible settings for the positioning time: 5 to 3,276
seconds. Default setting is 60 seconds.
run time OPEN