Operation instructions
SIPOS 5 PROFITRON, HiMod
Page 60 Y070.020/GB
7 Status and fault signals, diagnosis
7
Status and fault signals, diagnosis
No
Message Explanation Possible remedy
5
runtime error
3
After 3 % of the commissioning time, the
actuator has cover less than 0.5 % travel.
The positioning time is measured and sa-
ved for the set output speed for end position
adjustment.
Possible reasons:
Potentiometer contacts in the plug/ socket
connector were ejected.
Incorrect assembly and/or setting of the
potentiometer after an exchange.
Motor cable interrupted (motor is not
running).
Error during position recording (the gear
backlash between potentiometer and
central wheel is too small or too large: No
change of position is detected although
the motor is running).
Signaling gear ratio was changed
Signaling gear turns in the opposite
direction or
setting of the slide wheel (rev/stroke in
the signaling gear is to high).
Actuator is blocked (actuator cannot be
operated from position/end position).
Faulty potentiometer ( lm is interrupted).
• Parameter for separate mounting
„>10m with lter“ not set.
Check valve, signalling gear, motor and
potentiometer!
Check „Sep. mounting“ parameter.
22
setp. inp. Error
1
This message is only possible for
(4 – 20 mA) live-zero setting.
Threshold I: > 21 mA or < 3.6 mA.
Increase or reduce current,
check input current!.
20
voltage error
1,4
Supply voltage/electronics fault. Replace electronics.
27
watchdog error
4
Watchdog error. Replace electronics.
___________________________
1
Automatically resetting error.
2
Further action by the operator required at the actuator.
3
Fault can be acknowledged, refer to chapter 7.1.
4
Service required, refer to chapter 8.1.

Related product manuals