SKF Copperhead Transmitter Unit CMPT CTU 7-19
Basic Instructions and Wiring Connections
Normal Wiring as Vibration and Temperature (optional) Transmitter
Instruction Manual
Basic connections (Basic CMPT CTU with wiring):
Accelerometer CTU terminal
ACC Signal / Power (White) 1
ACC / TEMP signal Ground (Black) 2
TEMP signal High (Red) 3
Power +24 V DC 7
Power Ground 8
Analog output (current)
Vibration
4 to 20 mA 14
Vibration common 15
Temperature
4 to 20 mA 11
TEMP common 12
Alternative analog output (voltage)
Vibration
0 to 10 V DC 16
Vibration common 15
Temperature
0 to 10 V DC 13
TEMP common 12