6. Malfunctions, causes, and remedies
6
5
- 19 -
951-150-032-EN
Version 09
6. Malfunctions, causes, and remedies
Malfunctions table
Fault Possible cause Remedy
Mechanical blockage of the metering device Eliminate the blockage, check the metering device
Metering device
signal missing
Socket not connected or connected
incorrectly
Check plug contacts, mount the socket correctly
Signal line is broken
Check signal line
Piston detector is not installed correctly
Check engagement depth of adapter and piston detector, tighten if
necessary
Piston detector overtightened
Disconnect the piston detector, check the signal, replace the piston detector
if damaged
Wrong adapter used Use only the adapter approved for the respective metering device
A universal piston detector is being used instead of a
bipolar piston detector. (Only when connected to KFG
pumps for automotive lubrication.)
Swap the pigtail leads: see Chapter 3.3
Flashing light
Load is too low (< 5mA)
Increase the load by, for example, connecting a resistor in parallel in the
input circuit of the piston detector.
6.1 Metering devices signal missing