EasyManua.ls Logo

SKF Multilog IMx-S 32 - Unit Configuration Options; Analogue Inputs Configuration

SKF Multilog IMx-S 32
52 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SKF Multilog On-Line System IMx-S 3 - 1
User Manual Revision S
3
Unit Configuration
In general, when referring to DIP switch settings 0 means Off and 1 means On:
Table 3-1: DIP switch setting definition.
DIP Switch Setting
Definition
0
OFF
1
ON
Analogue Inputs
The figure below shows the screw terminal connections for the IMx-S.
Important - The sensor shield should be connected either to the sensor or to the
IMx-S unit depending on the cable and the sensor type. To avoid ground loops the
sensor shield should be connected only at one end.
Figure 3 - 1.
IMx-S Terminal Connection, Standard Accelerometer.
The IMx-S I/O board along with the corresponding analogue terminal list are shown
below.

Related product manuals