11 Troubleshooting
SMA Solar Technology AG
Operating manualSTP50-4x-BE-en-23100
Event number Message, cause and corrective measures
3801
3802
3803
3805
3806
3807
3808
DC overcurrent > Check PV array
Overcurrent at the DC input. The inverter briefly interrupts feed-in operation.
Corrective measures:
• If this message is displayed frequently, ensure that the PV array has been
correctly rated and wired.
4301
4302
Electric arc detected
The arc-fault circuit interrupter has detected an electric arc. If the arc-fault cir-
cuit interrupter is activated using operation inhibition, the operation inhibition
function must be reset manually.
6002-6412
Self-diagnosis > Device disturbance
The cause must be determined by the Service.
Corrective measures:
• Contact the Service.
6502
Self-diagnosis > Overtemperature
The inverter has switched off due to excessive temperature.
Corrective measures:
• Clean the cooling fins on the rear of the enclosure and the air ducts on
the top using a soft brush.
• Ensure that the inverter has sufficient ventilation.
• Ensure that the inverter is not exposed to direct solar irradiation.
6512
Minimum operating temperature not reached
The inverter will only recommence grid feed-in once the temperature has
reached at least −25°C.
6603
6604
Self-diagnosis > Overload
The cause must be determined by the Service.
Corrective measures:
• Contact the Service.