38 SB3-5TL-21-BE-en-10 Operating Manual
7 Initial Start-Up SMA Solar Technology AG
After the self-test has been completed, the inverter automatically switches back to the feed-in
operation, resets the original shutdown conditions and connects to the utility grid. The test takes
approx. three minutes.
Requirements:
Configured country data set: CEI 0-21 Int or CEI 0-21 internal or amended country data set
trimmed or special setting based on one of the country data sets mentioned above.
A report for entering the test results according to CEI 0-21 must be available.
The inverter must be in operation and in the start phase.
Procedure:
1. As soon as the configured country data set appears in the display, tap once on the display
within ten seconds.
A message informing you that the self-test has started is shown in the display:
Avvio Autotest.
✖The message Avvio Autotest is not shown in the display?
Ten seconds have passed and the self-test has not started.
Restart the self-test (see Section 7.5.2, page 39).
2. Tap on the display within 20 seconds and enter the test results that follow into the test report.
The self-test starts.
The inverter displays the results of the individual tests for overvoltage, undervoltage, maximum
frequency and minimum frequency. The results are displayed three times in succession for ten
seconds each.
The information Autotest interroto is shown in the display?
The self-test was cancelled due to an unexpected disconnection condition or the DC voltage was
too low so that the grid feed-in could not continue.
Restart the self-test (see Section 7.5.2, page 39).
Example: Display messages for overvoltage test
- Name of the test: Autotest (59.S1) 240.00V
- Disconnection value: Valore di soglia con 230.00V
- Normative value: Va. taratura 253.00V
- Disconnection time: Tempo die intervento 0.02 s
- Current line voltage: Tensione di rete Val.eff.: 229.80V