10 Function Description
SMA Solar Technology AG
User ManualSCCPXT-E7-BA-en-58108
The parameter PwrMonErrMod is used to configure whether the last default values (LastVal) or the configured
substitute values (SubVal) are to be used. This setting will be valid for both active and reactive power setpoints. The
substitute values are used when the time since receiving the last valid signal for default values as defined in the
parameter PwrMonErrTm has elapsed.
Setting Description
LastVal If specified via communication: utilization of the last value received
In case of analog setpoints: utilization of the last valid mean value
SubVal Use of configured substitute values
The use of the substitute values is recommended when setpoints are effected via analog sig-
nals.
P-WSubValRun: substitute value for active power limitation in feed-in operation
P-WSubVal: substitute value for active power limitation outside of feed-in operation
Q-VArSubValRun: substitute value for the reactive power setpoint in feed-in operation
PF-PFSubValRun: substitute value for the displacement power factor in feed-in
operation
PF-PFExtSubValR: substitute value for the excitation of the displacement power factor
in feed-in operation
Q-VArSubVal: substitute value for the reactive power setpoint outside of feed-in
operation
PF-PFSubVal: substitute value for the displacement power factor outside of feed-in
operation
PF-PFExtSubVal: substitute value for the excitation of the displacement power factor
outside of feed-in operation
10.4 Structure of the Communication Network
In order to connect the inverter to a computer via the service interface or via the Internet, the communication unit must
be integrated in a system network. To enable several inverters to be operated in the same network, the communication
unit of each inverter must be assigned a unique network address.