4 Commissioning
SMA Solar Technology AG
User ManualSCCPXT-E7-BA-en-5840
4.6.7.3 Activating the Manual Resume Mode
If the inverter is switched off due to a grid limit infringement, you can prevent an automatic restart of the inverter. Only
once the error has been acknowledged will the inverter switch back on. You can activate the Manual Resume Mode
for individual errors of grid limit infringement. You can read off the reason for the current restart block in the
instantaneous value ManResStt.
Procedure:
1. Call up the parameter overview (see Section9.3.1, page78).
2. To activate the Manual Resume Mode for individual disturbances, set the desired parameters to On:
Manual Resume Mode after Parameter
Disconnection due to overvoltage
ManResOvrVol
Disconnection due to undervoltage
ManResUndrVol
Disconnection due to overfrequency
ManResOvrFrq
Disconnection due to underfrequency
ManResUndrFrq
Disconnection due to passive islanding detection
ManResPID
Disconnection due to disturbance in a line conductor
ManResPLD
3. Save the parameter changes (see Section9.3.2, page78).
4.6.8 Setting the Grid Support
4.6.8.1 Setting Full and Limited Dynamic Grid Support (FRT)
1. Call up the parameter overview (see Section9.3.1, page78).
2. Set dynamic grid support with the parameter FRTEna.
3. Set operating mode for dynamic grid support with the parameter FRTMod.
4. Set deactivation delay for LVRT with the parameter FRTSwOffTm.
5. Set the scaling of the k factor for LVRT with the parameter FRTArGraNom.
6. Set the upper limit of the voltage deadband with the parameter FRTDbVolNomMax.
7. Set the lower limit of the voltage deadband with the parameter FRTDbVolNomMin.
8. In operating mode FRT_SDLWindV, set the gradient for the FRT characteristic curve in case of overvoltage with the
parameter FRT2ArGraNomHi.
9. For the operating mode FRT_SDLWindV, set the gradient for the FRT characteristic curve in case of undervoltage
with the parameter FRT2ArGraNomLo.
10. Save the parameter changes (see Section9.3.2, page78).
4.6.8.2 Setting Enable Islanding Detection
1. Call up the parameter overview (see Section9.3.1, page78).
2. Set the islanding detection with the parameter EnaAid.
3. Save the parameter changes (see Section9.3.2, page78).
4.6.8.3 Setting the Medium Voltage
The line-to-line voltage of the overvoltage side of the MV transformer (parameter TrfVolExlHi) has to be adapted to
the nominal conductor voltage of the utility grid (parameter VRtg). It is important that the transmission ratio of the
external MV transformer is adjusted at the same time. The undervoltage side is already preset for the specific device.