EasyManua.ls Logo

SMA SUNNY CENTRAL 800CP XT - Reactive Power Setpoint Via Displacement Power Factor Cos Φ: Pfcnst Mode; Displacement Power Factor Cos Φ Via Standard Signal: Pfcnstanin Mode

SMA SUNNY CENTRAL 800CP XT
156 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10 Function Description
SMA Solar Technology AG
User ManualSCCPXT-E7-BA-en-5896
Signal Power limit Description
11.5mA 0 kVAr Zero-crossing of the characteristic curve
No reactive power is fed in.
>19mA
Qmax / overexcited
End point of the characteristic curve
The maximum amount of positively excited reactive
power is fed in.
The analog value is converted to a setpoint for power limitation. Here, the parameter Qmax forms the end point of the
linear characteristic curve.
Figure 25: Limitation of the reactive power to the parameter Qmax
10.3.3.7 Reactive Power Setpoint via Displacement Power Factor cosφ: PFCnst Mode
The reactive power setpoint is set via the parameters PF‑PF and PF‑PFExt. The parameter PF‑PF indicates the
displacement power factor cosφ and the parameter PF‑PFExt indicates the degree of overexcitation or
underexcitation.
10.3.3.8 Displacement Power Factor cosφ via Standard Signal: PFCnstAnIn Mode
The reactive power setpoint is set at the input terminals for the setpoints via an analog signal. This is usually
implemented by a ripple control signal. The analog value is converted into a displacement power factor cos φ. The
electrical current strength of the connected signal determines the setpoint. The analog measured values must be
between 4mAand19mA. If the analog signal is less than 2mA, an error message will be displayed in the
instantaneous value Q‑VArModFailStt.
Signal Power limit Description
< 2 mA Last valid mean value or 0kVAr after
restart
Signal is in the invalid range.
2mA to 4mA
PFAbsMin/underexcited
The maximum amount of negatively excited reactive
power is fed in.

Table of Contents

Related product manuals