11 Operating Data and Parameters
SMA Solar Technology AG
User Manual 131SCCPXT-E7-BA-en-58
Name Description Value/range Explanation Default
value
Q-VArSubVal-
Run
Substitute value for reac-
tive power setpoint in
normal feed-in operation
during communication
disturbance
−245kVAr to
+245kVAr
SunnyCentral500CPXT 0kVAr
−310kVAr to
+310kVAr
SunnyCentral630CPXT
−346kVAr to
+346kVAr
SunnyCentral720CPXT
−365kVAr to
+365kVAr
SunnyCentral760CPXT
−385kVAr to
+385kVAr
SunnyCentral800CPXT
−409kVAr to
+409kVAr
SunnyCentral850CPXT
−433kVAr to
+433kVAr
SunnyCentral900CPXT
−485kVAr to
+485kVAr
SunnyCentral1000CPXT
Q-VLockInW** Voltage value from
which the Q(V) charac-
teristic curve is activated,
in% relative to the nomi-
nal voltage
0% … 100% ‒ 0%
Q-VLock-
OutW**
Voltage value from
which the Q(V) charac-
teristic curve is deacti-
vated, in% based on the
nominal voltage
0% … 100% ‒ 0%
Q-VLock-
InTm**
Waiting time for activa-
tion of the Q(V) charac-
teristic curve
0sto100s ‒ 2s
Q-VLock-
OutTm**
Waiting time for deacti-
vation of the Q(V) char-
acteristic curve
0sto100s ‒ 2s