11 Operating Data and Parameters
SMA Solar Technology AG
User ManualSCCPXT-E7-BA-en-58144
Name Description Value/range Explanation Default
value
DcCfg.AmpMax[4] Maximum current of
input 4
0A to 500A ‒ 0A
DcCfg.AmpMax[5] Maximum current of
input 5
0A to 500A ‒ 0A
DcCfg.AmpMax[6] Maximum current of
input 6
0A to 500A ‒ 0A
DcCfg.AmpMax[7] Maximum current of
input 7
0A to 500A ‒ 0A
DcCfg.AmpMax[8] Maximum current of
input 8
0A to 500A ‒ 0A
MaxTol Tolerance in percent
by which the input
current may deviate
from the mean value
0.1%…100% ‒ 4.0%
DevFunc Device function --- Default, no action ---
ResetMeasuring Restarts the algorithm. All measured
value are deleted.
Factory Resets all parameters to default set-
tings
Ackn Acknowledge errors --- Default, no action ---
Quit Acknowledgment of the present er-
ror
AlarmEna Activation of the error
analysis
--- Default, no action ---
Off No error analysis. Only measured
value are sent.
On Error analysis activated. Error mes-
sages are generated, if deviations
occur (see Section11.1.4.2,
page120).