Loading...
SMA Solar Technology AG 5 Technical Data
Installation Manual STP60-JP-10-IA-en-11 31
Table 5.1 Specifications
1)
at nominal grid voltage
2)
at nominal grid voltage, Cos(phi) = 1.
Table 5.2 Safety specifications
1)
depending on local regulations
Enclosure
Dimensions (W / H / D) 740 × 570 × 306 mm
Weight 75 kg
Acoustic noise level 58 dB(A) (typical)
Parameter STP 60-JP-10
Parameter STP 60-JP-10
Protection class (according to IEC 62109-1) I
Electrical
Electrical safety IEC 62109-1/IEC 62109-2 (Class I, grounded –
Communication part Class II, PELV)
Functional
Functional Safety Voltage and frequency monitoring
Monitoring of DC current share in AC current
Insulation resistance monitoring
FI monitoring
Islanding detection - grid failure Active frequency shift
Disconnection
Three-phase monitoring
•ROCOF/SFS
RCD compatibility
1)
Typ B, 1000 mA