5 Technical Data SMA Solar Technology AG
30 STP60-JP-10-IA-en-11 Installation Manual
5 Technical Data
5.1 Specifications
Parameter STP 60-JP-10
AC
Nominal apparent power
1)
60000 VA
Nominal active power
2)
60000 W
Reactive power range
1)
0 to 60000 var
Nominal AC voltage 3 / PE; 420 V (50 Hz)
3 / PE; 440 V (60 Hz)
Supported grounding systems TT, TN
Nominal AC current 3 x 82.5 A
Max. AC current at 400 Vac 3 x 87 A
AC total harmonic distortion (THD at nominal output power) < 1 %
Power factor – standard > 0.99 at nominal power
Displacement power factor 0 overexcited to 0 underexcited
Stand-by power consumption (for communication) 3 W
Nominal grid frequency (range) 50 Hz/60 Hz (± 10%)
DC
Maximum PV array power 90000 Wp
Input voltage range (at 420 Vac / at 440 Vac) 593 V to 1000 V / 622 V to 1000 V
Nominal voltage DC (at 420 Vac / at 440 Vac) 660 V / 690 V
MPP voltage range (at 420 Vac / at 440 Vac) 598 V to 800 V / 627 V to 800 V
Startup voltage (at 420 Vac / at 440 Vac) 628 V / 660 V
Max. input voltage 1000 V
Min. power on the grid 100 W
Max. input current / max. short-circuit current 110 A / 150 A
Number of independent MPP inputs /
strings per MPP input
1/2 (split up by external PV array junction box)
Overvoltage categories AC: Overvoltage category III (OVC III),
PV: Overvoltage category II (OVC II)
Efficiency
Max. EU efficiency 98.8 %
Efficiency in accordance with JIS C 8961 98 %
MPPT efficiency, static 99.9 %